Providing electronic overcurrent protection for single or three phase operation on systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting.
FEATURES
- Reliable performance
- Works directly with SEL-651R control
- Operator safety including mechanical block on trip and lockout handle
- Maintenance free operation
- Overhead, substation and dead-front padmount designs
- "L", "C" and "Z" style options
- Ease of Installation
- Ease of automation
- Internal voltage sensing and current transformers
- Application flexibility
- Various module configurations for circuit connection flexibility
- Smart Grid solutions
- RUS accepted
OPERATION OPTIONS
- DEAD LINE – Unique design of Viper-ST magnetic actuator system provides for local & remote operation if AC power is lost
- OPERATION PRINCIPLE – The Viper-ST recloser monitors the circuit using internal multi-ratio current transformers and voltage sensors. Sequence operations, tripping and overcurrent sensing is an automatic function. Each phase module incorporates a magnetic actuator and drive assembly. Control can be set for three distinct operating modes for maximum application flexibility
- MANUAL TRIP – Operation of the hookstick operable manual trip handle trips and locks out the recloser
For build options and site-ready designs, please contact TransNet.
TECHNICAL SPECIFICATIONS
VOLTAGE CLASS (kV) |
15 |
25 |
35 |
MAX SYSTEM VOLTAGE (kV) |
15.5 |
27 |
38 |
BIL (kV) |
110 |
125 |
150 |
CONTINUOUS CURRENT (A) |
800 |
8HR. OVERLOAD AT 20°C |
960 |
60Hz WITHSTAND, kV RMS DRY, 1 MIN |
50 |
60 |
70 |
60Hz WITHSTAND, kV RMS WET, 10 SEC |
45 |
50 |
60 |
INTERRUPTING RATING RMS (kA) |
12.5 |
MAKING CURRENT, RMS, ASYM, kA |
20 |
PEAK, ASYM (kA) |
32 |
SHORT CIRCUIT CURRENT, kA SYM, 3 SEC |
12.5 |
MECHANICAL OPERATIONS |
10K |